Four conditions for the generator set to be connected to the grid:
1. The frequency of the generator is the same as the system frequency.
2. The generator output voltage is the same as the system voltage, and the maximum error should be within 5%.
3. The generator phase sequence is the same as the system phase sequence.
4. The generator voltage phase is the same as the system voltage phase.
When the above four conditions are met, the grid-connected switch can be closed to allow the generator set to be connected to the system for operation.
If any of the above conditions is not met, the differential voltage will disappear at both ends of the switch K. If K is closed, the transient impact current will definitely disappear in the circuit composed of the generator and the grid.
Among the above conditions, except that the phase sequence is all positive conditions, the other conditions are relative, because the motor can usually withstand some small impact currents.
The preparatory work for grid connection is to check the grid connection conditions and determine the closing time. Usually, a voltmeter is used to measure the grid voltage, and the excitation current of the generator is adjusted so that the output voltage of the generator is U=U1. Then the frequency and phase are checked and adjusted with the help of the synchronization indicator to determine the closing time.
Advantages of grid-connected operation Grid power supply has many advantages over single-machine power supply:
① Improved reliability of power supply. A motor failure or regular maintenance will not cause a power outage.
② Improved economy and flexibility of power supply. For example, when a hydropower plant is connected in parallel with a thermal power plant, the two power plants can be allocated to generate electricity during the dry season and the peak season, so that water resources can be used reasonably. During peak and trough periods of electricity consumption, the number of generators put into the grid can be quickly planned, which improves power generation efficiency and power supply flexibility.
③ Improved power supply quality. The capacity of the grid is huge (relative to a single generator or individual load, it can be regarded as infinite). The input and shutdown of a single generator and the change of individual loads have little effect on the grid. The voltage and frequency that measure the quality of power supply can be regarded as constant constants.
The grid can be regarded as an infinite grid or an infinite bus for a single generator. After the synchronous generator is connected in parallel to the grid, its operating status is subject to the constraints of the grid, that is, its voltage and frequency must be the same as the grid and cannot change alone.